Request a quote
KlOG

Gas odorization complex “KlOG” (valve type)

Pulsed gravity dosing of odorant through solenoid valves in proportion to gas flow. Simple and reliable solution for stations of small and medium capacity.

Designed in accordance with EN 12186, ATEX 2014/34/EUGas odorization

The valve-type gas odorization complex “KlOG” is designed to supply micro-doses of odorant into the gas flow supplied to the consumer, in order to give natural gas a specific smell for timely detection of leaks.

The complex provides pulsed supply of odorant into the gas, under the weight of the odorant, by means of solenoid valves, based on the values of gas flow and odorant flow, while observing the required degree of gas odorization.

What the system provides

  • Maintaining the required degree of odorization
  • Automatic control and correction of each dose
  • Communication with the gas flow computer (pulse, RS-232/RS-485)
  • Operation by a constant flow value in the absence of communication
  • Odorant accounting: consumption and balance per hour, day, month, year
  • Alarms: no odorant supply, low/high level, sensor failure, no mains power
  • Automatic switch-over to backup power and battery charging
  • Backup (emergency) odorization unit — on request

Technical data

Process unit

Dosing methodPulsed, hydrostatic (by odorant weight) through solenoid valves
LocationExGDS site (explosive area)
OdorantsEthyl mercaptan C₂H₅SH or a mixture of natural mercaptans
Odorization rateg/1000 m³16 by default (adjustable)
Maximum pressure at the injection pointMPa1.6
Dosing error%≤ ±5
Odorant filtrationµmTwo-stage: 100 / 40
Ambient temperature°C−30 … +50
Protection degreeIP54

Control unit

ControllerIndustrial PLC, modular
ModesAutomatic (proportional to flow) / by constant
InterfacesRS-232 / RS-485, Modbus
ArchivesCurrent ≥ 72 h; emergencies and interventions ≥ 1 year
Main / backup supplyV~230 / =24
Operation from backup powerh≥ 72

Reliability

Service lifeyears≥ 12
Maintenance intervalyears2

Applications

Gas distribution stations of small and medium capacityGas reduction unitsReplacement of drip and wick odorizers
Request a quote

Request a quotation

Tell us about your site: gas flow rate, inlet and outlet pressure, required functions. We will prepare a technical proposal within 3 working days.

By submitting the form you agree to the processing of your data for the purpose of answering your request.